# Angus Fire TPS-50 Foam Top Pourer

- Link: https://fasco.pk/product/angus-tps-50-foam-top-pourer/
- Published: 2026-10-28T07:41:28+00:00
- Author: Fasco Pakistan

# Angus TPS-50 Foam Top Pourer

The **Angus TPS-50 Foam Top Pourer** is a fixed firefighting foam system component
designed to protect suitable fixed-roof flammable-liquid storage tanks. Manufactured
by Angus Fire, the Top Pourer Set combines foam generation, vapour sealing, and 
foam discharge functions in an integrated assembly. It is designed to introduce 
foam into the tank and direct the finished foam onto the liquid surface.

Foam top pourers are important components of fixed foam fire protection systems 
used in applications such as tank farms, oil refineries, and petrochemical installations.
When the system operates as designed, the foam is directed against a deflector so
that it flows onto the fuel surface with reduced application velocity. This helps
distribute the foam while reducing contamination caused by forceful discharge into
the stored liquid.

The Angus TPS-50 designation identifies a particular size within the Top Pourer 
Set range. Angus Fire has produced different generations, including the TPS Mk4 
and TPS Mk5. Their intended tank-pressure conditions and installation details differ,
so the exact version must be confirmed before purchasing or specifying the product.

## Key Features

### 1. Designed for Fixed-Roof Storage Tanks

The Angus TPS range is designed for foam protection of fixed-roof flammable-liquid
storage tanks. The appropriate model must be selected according to the tank design,
stored product, operating conditions, and applicable fire protection standards.

### 2. Integrated Foam Generation and Discharge

The Top Pourer Set combines foam generation and delivery functions. Its design helps
produce finished foam and direct it into the protected tank through the designated
discharge arrangement.

### 3. Controlled Foam Application

The internal deflector directs foam against the tank wall so that it can flow gently
over the stored liquid surface. This helps reduce the impact of the discharge on
the fuel and supports the intended foam application method.

### 4. Vapour-Sealing Arrangement

The TPS design incorporates a bursting-disc assembly that remains sealed during 
normal operation and opens when the system reaches its specified operating conditions.
This helps maintain the intended vapour-sealing function before activation.

### 5. Different Installation Options

Angus TPS units can be configured for different installation arrangements, including
standard and split-flange options. The appropriate arrangement depends on the tank
construction, available access, and installation requirements.

### 6. Model-Specific Performance

The TPS-50 has a defined operating performance envelope rather than one universal
flow rate. Flow varies with inlet pressure and the selected configuration. The manufacturer
datasheet should be used to identify the correct operating point for the project.

## Technical Specifications

The following information describes the Angus TPS-50 product family. Confirm the
exact Mk4 or Mk5 variant before treating the details as final specifications for
the supplied item.

 * **Product Name:** Angus Fire TPS-50 Foam Top Pourer
 * **Manufacturer:** Angus Fire
 * **Product Type:** Fixed foam top pourer / foam generator assembly
 * **Model Size:** TPS-50
 * **Product Generation:** Mk4 or Mk5 — to be confirmed
 * **Primary Application:** Fixed-roof flammable-liquid storage tanks
 * **Installation Options:** Standard or split-flange configuration, subject to 
   model
 * **Operating Pressure:** Model-dependent; check the relevant datasheet
 * **Flow Rate:** Pressure-dependent; check the TPS-50 performance envelope
 * **Foam Discharge Arrangement:** Internal deflector
 * **Vapour Seal:** Bursting-disc assembly
 * **Construction Materials:** Depend on model and material option
 * **Flange Standard:** Confirm the required ANSI or DIN configuration
 * **Approvals:** Verify the current approvals applicable to the exact model
 * **Country of Manufacture:** Confirm from supplier documentation

### TPS-50 Performance Information

Angus Fire’s published TPS Mk4 performance chart gives a pressure envelope of approximately
3–10 bar for the TPS-50, with flow varying across that range. Do not use a single
maximum flow value as the rated flow for every installation. The final flow and 
operating point must be specified for the selected unit.

## Applications

Subject to the equipment configuration and approved fire protection design, the 
Angus TPS-50 may be used in:

 * Fixed-roof flammable-liquid storage tanks
 * Oil and fuel storage tank farms
 * Petroleum refineries
 * Petrochemical facilities
 * Industrial liquid storage installations
 * Fixed foam fire protection systems designed for compatible hazards

The suitability of the unit depends on the stored liquid, tank construction, tank
pressure, required foam application rate, and applicable design standards.

## How to Select the Correct Angus TPS-50

### Confirm the Product Generation

Determine whether the project requires TPS Mk4 or TPS Mk5. The versions have different
intended tank-pressure conditions and installation considerations.

### Verify the Required Flow and Pressure

Use the manufacturer’s performance chart to establish the correct flow at the project’s
design pressure. Confirm the orifice disc and other configuration details specified
for the unit.

### Check the Tank Design

Verify that the pourer is suitable for the tank’s construction, internal pressure,
stored liquid, and foam system design.

### Select the Installation Arrangement

Confirm whether a standard or split-flange installation is required. The correct
mounting arrangement and flange dimensions should be established before ordering.

### Confirm Material and Approval Requirements

Check the selected construction material, seals, bursting-disc specification, and
current approvals against the project requirements and manufacturer documentation.

## Why Choose FASCO?

FASCO supplies firefighting and fire safety equipment for industrial and commercial
applications. For fixed tank foam protection, selecting the correct equipment configuration
is essential for ensuring that the product matches the system design and installation
requirements.

When enquiring about the Angus TPS-50, provide the tank dimensions, stored liquid,
required flow and pressure, flange standard, and the specified model generation.
This information helps confirm the correct product configuration.

## Buy Angus TPS-50 Foam Top Pourer from FASCO

Looking for an Angus Fire TPS-50 Foam Top Pourer for a fixed-roof storage tank? 
Contact FASCO to enquire about availability, product documentation, installation
options, and pricing.

Before placing an order, verify the Mk4 or Mk5 version, operating pressure, flow
specification, flange arrangement, and compatibility with the tank’s engineered 
foam protection system.

**Contact FASCO for technical details and a quotation.**