# C-TEC CFP708-4 8-Zone Conventional Fire Alarm Control Panel

- Link: https://fasco.pk/product/c-tec-cfp708-4-8-zone-fire-alarm-panel/
- Published: 2026-11-19T17:29:59+05:00
- Author: Fasco Pakistan

## C-TEC CFP708-4 8-Zone Conventional Fire Alarm Control Panel

The **C-TEC CFP708-4 Fire Alarm Panel** is an 8-zone conventional fire alarm control
panel designed to provide reliable fire detection monitoring and alarm management
in commercial, industrial and institutional buildings. Manufactured in the United
Kingdom, this panel belongs to C-TEC’s CFP conventional fire alarm series.

The panel monitors eight individual detector zones and provides four conventional
sounder circuits for audible warning devices. It combines a straightforward user
interface with useful installation and engineering functions, including zone testing,
selectable delays, coincidence detection and non-latching zone settings.

### Key Features of C-TEC CFP708-4

 * **Eight Detection Zones:** Monitors up to eight conventional fire detector circuits.
 * **Four Sounder Circuits:** Provides four separate conventional sounder outputs
   for connected alarm devices.
 * **Integrated Power Supply:** Includes a 1.5A EN54-4/A2-compliant switch-mode 
   power supply.
 * **Fire and Fault Relays:** Features two onboard relays for fire and fault signalling.
 * **Remote and Reset Outputs:** Includes two open-collector outputs for remote 
   and reset functions.
 * **Zone Testing:** Provides engineering facilities for testing individual detector
   zones.
 * **Coincidence Detection:** Supports configured coincidence operation for selected
   detection arrangements.
 * **Selectable Zone Delays:** Allows suitable zone delay settings according to 
   the system design.
 * **Non-Latching Zone Facility:** Supports configurable non-latching operation 
   on selected zones.
 * **User-Friendly Interface:** Features colour-coded controls and combined keypad/
   keyswitch access.
 * **System Expansion:** Supports compatible repeaters, relay expansion boards and
   sounder interface options.
 * **Flexible Installation:** Supplied in a plastic enclosure suitable for flush
   or surface mounting.

### Technical Specifications

  |  Specification |  Details |  
 |  Brand |  C-TEC |  
 |  Series |  CFP |  
 |  Model |  CFP708-4 |  
 |  Product Type |  Conventional Fire Alarm Control Panel |  
 |  Number of Zones |  8 |  
 |  Sounder Circuits |  4 |  
 |  Mains Supply |  230V AC, 50/60Hz |  
 |  Maximum Mains Rated Current |  350mA |  
 |  Internal Power Supply |  27V nominal |  
 |  Power Supply Output |  1.5A |  
 |  Maximum Devices per Zone |  25 detectors or 32 detectors/manual call points combined |  
 |  Maximum Zone Circuit Length |  500 metres |  
 |  Maximum Sounder Output |  4 × 200mA (800mA total) |  
 |  Backup Battery |  2 × 12V 3.2Ah VRLA batteries |  
 |  Auxiliary Relays |  Fire and Fault |  
 |  Open-Collector Outputs |  Remote and Reset |  
 |  Mounting |  Flush or Surface |  
 |  Enclosure Protection |  IP30 |  
 |  Dimensions |  380 × 235 × 96mm |  
 |  Operating Temperature |  -5°C to +40°C |  
 |  Relative Humidity |  Up to 95% RH, non-condensing |  
 |  Country of Manufacture |  United Kingdom |

### Certifications and Standards

The C-TEC CFP708-4 is certified to the following fire alarm standards:

 * **EN54-2:** Control and indicating equipment.
 * **EN54-4:** Power supply equipment.
 * **EN54-13:** Compatibility and connectability assessment of system components.

The manufacturer’s published information identifies LPCB certification for EN54-
2 and EN54-4, and Kiwa Telefication certification for EN54-13.

### Applications

The C-TEC CFP 8-zone conventional fire alarm panel is suitable for installations
requiring a conventional fire detection system, including:

 * Commercial buildings and office premises
 * Retail shops and shopping facilities
 * Schools and educational institutions
 * Warehouses and storage facilities
 * Industrial buildings and workshops
 * Hotels and other commercial properties

### Installation and System Compatibility

The CFP708-4 is designed for conventional fire detection devices and compatible 
conventional sounders. It is also listed as compatible with C-TEC’s ActiV range 
of conventional fire detectors, sounders and visual alarm devices.

Each zone monitors a circuit of connected devices rather than assigning an individual
address to every detector. Confirm the required detector type, call point resistor,
end-of-line resistor, sounder load and battery capacity before installation.

The panel supports compatible expansion equipment, including repeaters and relay
expansion boards. Always check the manufacturer’s documentation for the correct 
accessories and system configuration.

Explore additional detection products, alarm panels and accessories in our [**Fire Alarm Systems**](https://fasco.pk/product-category/fire-alarm-systems/)
category.

### Why Choose the C-TEC CFP708-4?

The C-TEC CFP708-4 combines eight conventional detection zones, four sounder circuits
and integrated power supply equipment in one control panel. Its testing functions,
programmable zone behaviour and expansion options make it a practical choice for
compatible conventional fire alarm installations.

**Brand:** C-TEC
 **Series:** CFP **Model:** CFP708-4 **Product Type:** 8-Zone Conventional
Fire Alarm Control Panel **Manufactured in:** United Kingdom